August 2009: TB 3203 - Marstair Overload and Contactor Bulletin

Marstair Technical Bulletin         23/08/2009

Compressor overloads – Ranges and settings

Please refer to the table below for a complete list of overload part numbers and settings. Any changes to factory settings will be implemented from week 35 of 2009, with the starting unit serial number: 2165864.

Please note, that equipment employing previously recommended overload settings may be expected to function correctly at normal operating conditions.

 

MCU+/MRC/CKC Kit 1 Phase Setting (A) MHPUE/MHPUL Kit 1 Phase Setting (A)
15 55023233 6.2 15 55023233 6.2
20 55023233 8.1 30 55023234 9.2
30 55023234 9.2 40 55023234 12.4
40 55023234 12.4 50 55023235 14.3
50 55023235 14.3 60 55023235 21.6
60 55023235 18.5 80 55023235 21.6
80 55023235 21.6 90 55023247 26.0
90 55023247 26.0
DCU+/DCUE Kit 1 Phase Setting (A) DHPUE/DHPUL Kit 1 Phase Setting (A)
15 55023233 6.2 15 55023233 6.2
20 55023233 8.1 30 55023234 9.2
30 55023234 9.2 40 55023234 12.4
40 55023234 12.4 50 55023235 14.0
50 55023235 14.3 60 55023235 19.5
60