Marstair Technical Bulletin 23/08/2009
Compressor overloads – Ranges and settings
Please refer to the table below for a complete list of overload part numbers and settings. Any changes to factory settings will be implemented from week 35 of 2009, with the starting unit serial number: 2165864.
Please note, that equipment employing previously recommended overload settings may be expected to function correctly at normal operating conditions.
| MCU+/MRC/CKC | Kit 1 Phase | Setting (A) | MHPUE/MHPUL | Kit 1 Phase | Setting (A) |
| 15 | 55023233 | 6.2 | 15 | 55023233 | 6.2 |
| 20 | 55023233 | 8.1 | 30 | 55023234 | 9.2 |
| 30 | 55023234 | 9.2 | 40 | 55023234 | 12.4 |
| 40 | 55023234 | 12.4 | 50 | 55023235 | 14.3 |
| 50 | 55023235 | 14.3 | 60 | 55023235 | 21.6 |
| 60 | 55023235 | 18.5 | 80 | 55023235 | 21.6 |
| 80 | 55023235 | 21.6 | 90 | 55023247 | 26.0 |
| 90 | 55023247 | 26.0 | |||
| DCU+/DCUE | Kit 1 Phase | Setting (A) | DHPUE/DHPUL | Kit 1 Phase | Setting (A) |
| 15 | 55023233 | 6.2 | 15 | 55023233 | 6.2 |
| 20 | 55023233 | 8.1 | 30 | 55023234 | 9.2 |
| 30 | 55023234 | 9.2 | 40 | 55023234 | 12.4 |
| 40 | 55023234 | 12.4 | 50 | 55023235 | 14.0 |
| 50 | 55023235 | 14.3 | 60 | 55023235 | 19.5 |
| 60 |